Box Fill Calculator
Verifies conductor, fitting, and device count fit within outlet or junction box per NEC 314.16.
Conductors
Devices, Clamps & Grounds
Results
Fill Breakdown
Based on NEC 314.16 and Table 314.16(B). Verify with your local AHJ.
Save this calculation to your account
Create a free account to save your results, compare sizing options side by side, and download a branded PDF you can attach to a quote.
Save this calculation to your account
Email these results to yourself
Get a copy you can reference on the job site or attach to a quote.
Results sent! Check your inbox.
Want to save all your calculations?
How to Use This Calculator
1. Select the box type and size. Common residential boxes are single gang 18 cu in. Junction boxes are typically 4" square or round.
2. Enter conductor counts by gauge. Count every wire entering the box. Pigtails made inside the box do not count unless they leave the box.
3. Add devices, clamps, and grounds. Each device (switch/outlet) counts as 2 volumes. All clamps together count as 1 volume. All grounds together count as 1 volume.
NEC 314.16 Volume Allowances
#14 AWG: 2.00 cu in per conductor
#12 AWG: 2.25 cu in per conductor
#10 AWG: 2.50 cu in per conductor
#8 AWG: 3.00 cu in per conductor
#6 AWG: 5.00 cu in per conductor
Device: 2x volume of largest conductor connected
Clamps: 1x volume of largest conductor (total, not each)
Grounds: 1x volume of largest ground (total, not each)
Fittings: 1x volume of largest conductor (total)
Frequently Asked Questions
How do you calculate box fill per NEC 314.16?
What are the NEC box fill volumes by wire size?
Does the ground wire count for box fill?
Related Electrical Tools
Conduit Fill
Check conduit fill per NEC Chapter 9. Supports EMT, PVC, RMC, and all wire types.
TechnicalWire Size Calculator
Find the right AWG for any circuit with NEC ampacity and voltage drop checks.
TechnicalPanel Load
Calculate service demand load per NEC Article 220 with demand factors.
TechnicalVoltage Drop
Calculate voltage drop by wire gauge, distance, and load. NEC compliance check included.