Technical Free

Wire Size Calculator

Determines correct wire gauge (AWG) based on load current, distance, voltage, and NEC derating factors. Returns ampacity and voltage drop verification.

Results

Recommended Wire
--
Derated Ampacity
--
Voltage Drop
--
Voltage at Load
--

Based on NEC 2023 Table 310.16 and Chapter 9. Verify final design with your local AHJ.

📊

Save this calculation to your account

Create a free account to save your results, compare sizing options side by side, and download a branded PDF you can attach to a quote.

Email these results to yourself

Get a copy you can reference on the job site or attach to a quote.

How to Use This Calculator

1. Enter the load current. This is the circuit amperage from the breaker or the connected load. For motors, use the nameplate FLA.

2. Set voltage and circuit type. Most residential is 120V or 240V single-phase. Commercial often uses 208V or 480V 3-phase.

3. Choose conductor material and insulation. Copper with THHN (90 degrees C) is the most common for commercial work. NM-B is standard for residential in-wall wiring.

4. Set the number of current-carrying conductors. If more than 3 CCC share a raceway, the calculator applies NEC derating factors automatically.

5. Enter the one-way run distance. The calculator checks voltage drop and flags if it exceeds your selected limit (3% for feeders, 5% for branch circuits).

How the Wire Sizing Formula Works

The calculator starts with NEC Table 310.16 base ampacities for each wire gauge at the selected insulation temperature. For continuous loads, it multiplies the load current by 1.25 per NEC 210.20.

Required_Ampacity = Load_Current x Continuous_Factor

Derated_Ampacity = Base_Ampacity x Conduit_Fill_Factor

Wire = Smallest AWG where Derated_Ampacity ≥ Required_Ampacity

VD% = (Multiplier x I x D x R) / (V x 1000) x 100

The conduit fill derating factor reduces ampacity when more than 3 current-carrying conductors share a raceway: 80% for 4-6 CCC, 70% for 7-9, 50% for 10-20, and 45% for 21-30.

After selecting the wire for ampacity, the calculator verifies voltage drop using NEC Chapter 9 Table 8 resistance values. If the voltage drop exceeds the limit, it recommends the next size up.

Frequently Asked Questions

How do I determine the correct wire size for a circuit?
Start with the load current, then apply NEC Table 310.16 to find the minimum AWG that meets the ampacity requirement after derating for temperature and conduit fill. Then verify voltage drop is within 3% for feeders or 5% for branch circuits. Always use the larger wire size if ampacity and voltage drop requirements differ.
What is the difference between copper and aluminum wire sizing?
Aluminum wire has lower ampacity than copper for the same gauge. For example, #6 copper carries 65A while #6 aluminum carries 50A at 75 degrees C. Aluminum is cheaper per foot but requires a larger gauge, anti-oxidant compound, and rated connectors.
When do I need to apply conduit derating factors?
Per NEC 310.15(B)(3)(a), when more than 3 current-carrying conductors are in a raceway or cable, you must derate the ampacity. 4-6 conductors derate to 80%, 7-9 to 70%, and 10-20 to 50%. This is one of the most commonly missed code requirements.
What AWG wire do I need for a 30 amp circuit?
For a 30-amp circuit, you typically need #10 AWG copper wire (rated 35A at 75 degrees C per NEC 310.16). If using aluminum, you need #8 AWG. Always verify with the actual installation conditions including temperature, conduit fill, and distance for voltage drop.

Related Electrical Tools

← View all Electrical tools