Technical Free · No login required

ACH Calculator

Calculates air changes per hour for any room. Verify ventilation meets ASHRAE and building code minimums.

Room Type Reference

Room Type Min Rec.
Bedroom45-6
Living Room45
Kitchen77-8
Bathroom67-8
Office45-6
Commercial68-12
Restaurant1015-20
Server Room1517-20

How to Use This Calculator

1. Choose your calculation mode. Use "ACH from CFM" if you know the current airflow and want to see if it's adequate. Use "CFM from ACH" if you have a target ventilation rate and need to know the required airflow.

2. Enter room dimensions. Measure the length, width, and ceiling height in feet. For irregular rooms, approximate the closest rectangular dimensions.

3. Enter airflow or target ACH. In ACH mode, enter the measured or rated CFM from the supply registers. In CFM mode, enter the desired ACH from the reference table.

4. Review the results. Check the color-coded ACH rating against the room type reference table and verify ASHRAE compliance status.

How ACH Works

Air changes per hour (ACH) measures how many times the entire volume of air in a room is replaced in one hour. It is the standard metric for evaluating ventilation adequacy and indoor air quality.

ACH = (CFM x 60) / Room_Volume

Required_CFM = (Room_Volume x Target_ACH) / 60

Higher ACH means fresher air but also higher energy costs, because you are conditioning more outside air. The goal is to hit the right range for each room type. A bedroom at 4-6 ACH is comfortable and healthy. A commercial kitchen below 10 ACH will have grease buildup, odor complaints, and code violations.

ACH matters for IAQ because it directly controls the dilution of indoor pollutants, CO2, moisture, and volatile organic compounds. Rooms with inadequate ACH develop stale air, condensation problems, and occupant complaints. Rooms with excessive ACH waste energy and can create uncomfortable drafts.

When HVAC Pros Use This

Ventilation system design. Before specifying fans, ductwork, or ERVs, you need to know the target ACH for every room. This calculator converts those targets into CFM values you can use for equipment selection and duct sizing.

IAQ complaint investigation. When a customer reports stuffiness, odors, or moisture issues, measuring the actual CFM and calculating ACH tells you immediately whether the room is under-ventilated. If a bathroom is running at 3 ACH when it needs 7, you have found the problem.

Code compliance verification. Building inspectors and commissioning agents use ACH to verify that mechanical ventilation meets ASHRAE 62.1 (commercial) and 62.2 (residential) requirements. This calculator flags whether the ACH meets those minimums.

Frequently Asked Questions

What is a good ACH for a house?
Most residential rooms need 4-6 ACH. Bedrooms and living rooms are fine at 4-6, kitchens need 7-8, and bathrooms need 6-8. Higher ACH means fresher air but also higher energy cost, so aim for the recommended range for each room type.
How do I calculate air changes per hour?
ACH = (CFM x 60) / Room Volume. First calculate the room volume (length x width x ceiling height in feet). Then multiply the airflow in CFM by 60 and divide by the volume. For example, 200 CFM in a 1,344 cu ft room = (200 x 60) / 1344 = 8.9 ACH.
What ACH is required for bathrooms?
Bathrooms require a minimum of 6 ACH, with 7-8 ACH recommended. ASHRAE 62.2 requires continuous exhaust of 20 CFM or intermittent exhaust of 50 CFM for residential bathrooms. Higher ACH helps control moisture and prevent mold growth.
What's the difference between ACH and CFM?
CFM (cubic feet per minute) measures raw airflow volume. ACH (air changes per hour) measures how many times the room air is fully replaced per hour. ACH accounts for room size, so a small room with 100 CFM has more air changes than a large room with 100 CFM. ACH is more useful for evaluating ventilation adequacy.

Related HVAC Tools

← View all 24 HVAC tools